TERM-007

Thin-film intumescent fire-protective coating for load-bearing steel structures. Applied up to 2000 µm in a single pass, raising fire resistance to 120 minutes.

TERM 007 — STATERM
  • Intumescent fireproof coating for steel structures.

    It is a thin-layer fire-protective coating system for steel load-bearing structures that foams under heat during a fire. The fire-resistant low-conductivity foam formed by heat exposure reduces the rate of temperature rise of the load-bearing steel structure. The coating has high stability of properties and a long service life.

    The base product of the range. In permanently dry rooms it is used on its own; on structures exposed to the weather it works as part of a system with a protective topcoat. If an extra layer in the system is undesirable, the weather-resistant TERM-009 is available for outdoor structures.

  • – the material is applied up to 2000 µm thick in one pass, reducing labour and time

    – low material consumption

    – does not create additional static load on structures

    – the material is certified in the Republic of Uzbekistan to raise the fire-resistance limit of steel structures up to 120 minutes.

    – easy application with airless spray equipment, brush or roller.

    – made in Uzbekistan

    – suitable for both steel and galvanised structures; on galvanising an intermediate adhesion primer is used

  • Used to increase the fire-resistance limit of steel load-bearing structures such as columns, trusses, bracings, struts and other structural load elements.

    Applied to steel and galvanised structures. On galvanising an intermediate adhesion primer is mandatory.

    The TERM-007 fire-protective topcoat is applied to a surface previously coated with an anti-corrosion primer.

    A topcoat of protective enamel is applied over the fire protection: in permanently dry rooms it is not required; in damp rooms — one layer of at least 50 µm; on outdoor structures — two layers, at least 100 µm in total. It is the topcoat that protects the fire-protective layer from the weather, so outdoors it is mandatory.

    If the structures work outdoors and the extra topcoat is undesirable, use the weather-resistant TERM-009 instead: it needs no topcoat.

  • ApplicationSteel and galvanised load-bearing structures: columns, trusses, bracing, struts and other structural members
    TypeThin-film intumescent fire-protective coating
    Fire resistanceTested in the Republic of Uzbekistan for limits up to 120 minutes
    ColourWhite
    Packaging20 kg
    Densityapprox. 1.50 g/cm³
    Solids by weight70 ± 3 %
    Dry film thicknessDepends on the section factor of the steel member and the required fire-resistance limit. Primer and topcoat thickness is not counted
    Substrate temperature+5 °C to +40 °C
    Relative humidity30–80 % during application; temperature must be 3 °C above the dew point
    Application methodBrush, roller, conventional and airless spray
    Airless sprayPressure ratio 45:1, pump output 4–5 l/min, nozzle 0.53–0.66 mm, hose over 9.5 mm; remove screens and filters
    Dryingapprox. 24 h per coat at +10…20 °C and 65 % humidity; at least 72 h before applying the topcoat
    ThinnerFresh water; thinning is normally not required, up to 5 % by weight is allowed
    System on steelPrimer Stacor UR, Stacor EP or GF-021 → TERM-007 → topcoat Stacor UR
    System on galvanised steelIntermediate adhesion primer Stacor UR is mandatory → TERM-007 → Stacor UR
    TopcoatNot required in permanently dry interiors; in damp interiors — 1 coat of at least 50 µm; outdoors — 2 coats, at least 100 µm in total
    Shelf life12 months in unopened factory packaging at +5…+30 °C
    Tool cleaningWater immediately after use